HVAC Infrared NP-Series Technical Data

Overview  •   Features & Benefits  •   Technical Data  •   Applications  •   Downloads

Infrared Heater - Negative Pressure NP Series

MODEL   CTHN - 40 CTHN - 60 CTHN - 80 CTHN - 100 CTHN - 125 CTHN - 150 CTHN - 175 CTHN - 200
Minimum Length of Straight Tube* [ft A] 10 20 20 30 40 40 50 50
Minimum Length of U-Tube* [ft ,in B ] 11, 6 11, 6 11, 6 16, 6 21, 6 21, 6 26, 6 26, 6
Overall Minimum Length of Straight Tube* [ft, in C ] 12, 3 22, 3 22, 3 32, 3 42, 3 42, 3 52, 5 52, 2
Minimum Length of U-Tube* [ft, in D ] 13, 2 13, 2 13, 2 18, 2 23, 3 23, 3 28, 2 28, 2
*For additional lengths, please see the current Installation, Operation and Service Manual.

Input (Btu/h) x (1000) 40 60 80 100 125 150 175 200
Inlet Pressure [in wc] NG min. 4.6 4.6 4.6 4.6 4.6 4.6 5 5
LPG Propane min.
11 11 11 11 11 11 11 11
NG & LPG Propane Max.
14 14 14 14 14 14 14 14
Gas Connection NPT ½" ½" ½" ½" ½" ¾" ¾" ¾"


Weights  
Overall Length of Tube
Accessory Packages
[ft] 10 20 30 40 50 60 70 80
Hot Rolled or Aluminized
Tube with Aluminum Reflector
[lb] 52 86 120 161 206 240 281 322
Aluminized Tube with
Stainless Steel Reflector
[lb] 66 113 152 208 265 304 360 416
Burner [lb] 35
Aluminized U-Tube
with Aluminum End Caps
[lb] 19
Aluminized U-Tube with
Stainless Steel End Caps
[lb] 20
Fuel   NG or LPG Propane
Electrical Supply   120 V, 60Hz, 1 A for 40 - 150; 120 V, 60 Hz, 2 A for 175 & 200
Heat Exchanger Tubing   10 ft Sections, 4" dia, 16 Gauge, First 10 ft ALUMI-THERM® Steel Tubing
[Remaining Hot Rolled, Heat Treated Aluminized Steel Tubing]
Exhaust Flue dia 4" See Installation, Operation and Service Manual for details
Reflector and End Caps   .024 Aluminum [Optional - .024 Stainless Steel Type 304]
Control System   Fully Automatic, Three-Try, Direct Spark, 100% Shut-Off, Electronic Ignition Control
Approved As   Indoor (Vented or Unvented)
Certification   ANSI Z83.20/CSA 2.34, 2.17
Warranty   Three-Year Limited (Refer to Installation, Operation and Service Manual for Details)


Clearances to Combustibles***
Horizontal 45°

Model CTHN-40 CTHN-60 CTHN-80 CTHN-100 CTHN-125 CTHN-150 CTHN-175 CTHN-200
  Horiz. 45° Horiz. 45° Horiz. 45° Horiz. 45° Horiz. 45° Horiz. 45° Horiz. 45° Horiz. 45°
A 5 8 5 8 5 9 5 10 5 10 5 10 8 10 8 10
B 20 4 27 4 30 4 32 4 35 4 39 4 44 4 47 4
C 41 35 51 45 58 54 60 57 65 63 71 66 74 69 76 73
D 20 43 27 45 30 55 32 56 35 58 39 61 44 68 47 17

***Clearances B, C and D can be reduced by 50% for locations 25ft (7 m) or more downstream of the burner. For other mounting options and associated clearances, complete installation, operation and service criteria, please see the current issue of the Installation, Operation and Service Manual.